Short-reach singlemode reduces cost yet demands ultra-low loss, high-performance connectivity

THE ARTICLES ON THESE PAGES ARE PRODUCED BY BUSINESS REPORTER, WHICH TAKES SOLE RESPONSIBILITY FOR THE CONTENTS

Provided by
Wednesday 10 April 2024 15:46 BST
Connect up: Cost-effectively supporting higher-speed applications in distances beyond 100 metres is now feasible
Connect up: Cost-effectively supporting higher-speed applications in distances beyond 100 metres is now feasible ( iStock)

Siemon is a Business Reporter client.

Singlemode fibre has become the cabling of choice for todayโ€™s higher-speed applications in hyperscale and cloud data centres, and increased purchase volumes are helping drive down overall equipment costs.

Still, expensive high-power, edge-emitting lasers used in long-distance LR and ER singlemode applications that support 10km and 40km lengths do not economically make sense for most data centres, where link lengths are much shorter. At the same time, multimode applications that rely on more cost-effective vertical-cavity surface-emitting lasers (VCSELs) are limited to distances of just 100 metres for transmission speeds above 40G, which presents a challenge for many larger data centres.

Cost-effectively supporting higher-speed applications in distances beyond 100 metres is now feasible with new 100G, 200G and 400G short-reach singlemode applications that use power-conserving lasers. However, the relaxed specifications of these applications come with stringent insertion loss budgets and new return loss considerations that demand ultra-low loss, high-performance singlemode cabling systems.

Cutting costs and extending distances

With less power and associated energy consumption and heat generation, power-conserving lasers used for short-reach singlemode applications are significantly less expensive than long-distance singlemode lasers. While preliminary options for these applications were based on non-return-to-zero (NRZ) signalling schemes with a 25G per lane bit rate, the development of the four-level pulse amplitude modulation (PAM4) signalling scheme that enables 50 and 100G per lane bit rates paved the way for the IEEE to introduce data centre reach (DR) and fibre reach (FR) singlemode applications with distances of 500m and 2000m, respectively. These include 500-meter duplex 100GBASE-DR and parallel optic 200GBASE-DR4 and 400GBASE-DR4 applications and 2000-metre wave division multiplexing (WDM) 200GBASE-FR4 and 400GBASE-FR4 applications.

With short-reach singlemode, the total cost of a 500-metre duplex 100GBASE-DR system now costs less than a 100-metre parallel optic 100GBASE-SR4 multimode system. Due to the cost savings, short-reach DR and FR singlemode applications are expected to rapidly gain ground in enterprise data centres as they migrate to 100, 200 and 400G speeds in backbone switch-to-switch links. They also support cost-effective breakout configurations where a single 200G switch port breaks out to four 50G connections or a single 400G switch port breaks out to four 100G connections, thereby optimising port utilisation and switch density for a reduced cost. The IEEE Beyond 400Gb/s Ethernet Study Group has also included DR and FR applications as part of the physical layer objectives for 800G and 1.6 terabit applications, which makes these applications also well positioned for cloud and hyperscale data centres that are migrating to 400 and 800G backbone switch-to-switch links and 50, 100, and 200G horizontal switch-to-server links.

Verified performance matters

Long-distance singlemode LR and ER fibre applications offer ample insertion loss budgets that can reach 18 dB, but the relaxed specifications for short-reach singlemode applications require far more stringent insertion loss budgets. IEEE standards specify a maximum channel loss of 3 dB for DR applications and 4 dB for FR applications. High-speed short-reach singlemode transceivers are also more susceptible to reflectance, which necessitated IEEE to specify reflectance values for short-reach singlemode applications based on the number of mated pairs in the channel. For example, if the reflectance of mated connectors in a 400GBASE-DR4 application is -45 dB, only four connectors can be included in the channel. With an improved reflectance of -49 dB, 10 connectors can be included. The maximum channel insertion loss is decreased if the discrete reflectance requirements cannot be met.

To ensure sufficient margin to accommodate variables such as poorly installed cabling, contaminated end faces, misalignments, aging transmitters, and other factors, data centre designers need to carefully review insertion loss and reflectance specifications for components such as jumpers, trunks, modules and adapters. In doing to, they should use only verified maximum values and avoid vendors that only publish typical values since typical values are generated primarily for marketing purposes and not guaranteed as a true indication of performance.

Data centre designers also need to consider the number of connections in a channel, such as the use of four-connector cross-connect channels that enhance flexibility, management, scalability and security. Many standard loss systems will not support the tighter loss budgets of short-reach singlemode applications in this configuration, and even some low loss systems will not provide sufficient margin. In fact, third-party testing has demonstrated that only ultra-low loss LC connectors with a verified maximum insertion loss of 0.20 dB and minimum reflectance of -65 dB and ultra-low loss MPO connectors with a verified maximum insertion loss of 0.30 dB and minimum reflectance of -60 dB support the use of cross-connects and provide sufficient channel margin in short-reach DR and FR singlemode deployments.


Discover more:ย siemon.com